Assessing control valves and their performance

Author: Morgan

May. 27, 2024

64

0

0

Assessing control valves and their performance

When assessing control valves and their performance, you need to understand the different types of valves and what they can be tested for. For open/close shutoff valves without analog control the tests are pretty simple. Do the valves open and close? When open, do they open all the way? When they close, do they close completely? Testing is mostly observational: looking at the valve and watching cause and effect in the process during the cycle.

Contact us to discuss your requirements of valve test table. Our experienced sales team can help you identify the options that best suit your needs.

Control valves are a different "beast" altogether

These valves open and close proportionally, and vary the degree of travel depending on the percent of span of the 4 to 20 mA signal applied to them. Observing the valve's position, as reported on the visual travel indicator, gives the technician or operator a rough indication of percent of travel for a particular setting when in operation - but does not provide any assurance of how the valve will operate under dynamic and changing conditions.

The most sophisticated valve performance tests require removing the valve and testing its performance on a "valve prover." This is an expensive test device, out of range for most instrument shops. The valve prover is often only used by valve manufacturers in testing the valve when shipped, or by highly qualified field service engineers. It offers a very complete test, but the tool is not feasible for most instrument shops.

So, what is the technician to use for testing a control valve?

What is a meaningful test that can be used as a baseline? Since most valves use a 4 to 20 mA input signal, any test tool with an mA output signal can provide the input mA signal to drive the control valve across its operating range. When applying a 3.8 mA input signal to a normally closed valve, the valve should be hard closed. It should remain closed at 4.0 mA and move slightly off its seat at 4.2 mA. At the other end of its operation, at 19.8 mA, it should be nearly full open. At 20.0 mA it should be fully open, and hard open at 20.2 mA (resting on the travel stop). Tests of this nature will determine if the valve is opening and closing correctly, but still fall short of testing the valve across the entire range where it provides control.

Many valves, including those that are "smart," have a feedback element built in that outputs the actual position as a percentage of open/close. This output can be a 4 to 20 mA signal or a digital HART variable that represents 0 to 100 percent of control valve operating span. Applying a varying mA signal, while simultaneously monitoring the output mA or percentage of span signal, gives a technician a means to see whether a control valve is operating correctly over its range. By recording simultaneously the applied mA signal and the output mA signal or PV percentage of span, the valve's performance can be documented. This documented test and result is often called a valve's "signature." The output should smoothly mirror the applied mA input signal. Any deviation from the applied signal is a potential indication of aberrant behavior by the valve.

Maintenance strategy can reduce costs

Jim Shields, product marketing manager at Fluke, says a best-in-class maintenance strategy for control valves can reduce costs by both minimizing the number of valves pulled physically from processing and minimizing failure risks. Here's his advice. To establish such a practice, the baseline condition of the valve at a known good state needs to be documented. Ideally the documentation occurs when the valve is commissioned or after it is overhauled. The technician records the signature of the valve in the ideal state, plotting the output mA or percentage of span signal versus applied input signal, and stores this information with the time, tag number of the valve, and the date the activity is performed. Calibration management software can be used to manage this information.

Once the baseline performance signatures of the valves are recorded, a maintenance interval for testing the performance of the valves needs to be established. Using existing maintenance intervals is a starting point. If there is no established maintenance interval, the service location of the valve needs to be evaluated. Rough service applications dictate a shorter maintenance interval than light duty service, for example. An interval of six months to a year to start (unless the service location is very hard on the valves) is a reasonable starting point. Some devices installed in safety and shut-down systems need to be checked every three months regardless of service location.

Once baseline valve signature data is recorded, the valves need to be tested at the defined intervals and the signatures recorded. The signatures can be compared to the baseline signatures to determine changes in their performance. If the output response curve has developed a nonlinear signature or has aberrations in the curves, the valve may be developing excessive stiction or hysteresis that may require it to be removed for service.

Valve Testing - Hydrostatic, Pneumatic, Shell, Seat, Fire...

Valve Testing &#; Hydrostatic, Pneumatic, Shell, Seat, Fire&#;

The realization of safe and smooth operations of industrial processes is heavily reliant on valves performing their function with precision. Thus, valve testing ensures that these valves meet design specifications for the duration of their operational life.

Generally, valve testing simulates operating conditions in a controlled environment to ensure fit for service valves. However, testing also occurs periodically after installation in line with standard practices.

In this article, we will review common valve testing types and industry standards that offer guidelines for valve testing.

There are several types of testing to which a valve could undergo. The required test depends on the application, manufacturer standards, and customer specifications. The following sections examine common tests, an overview of their procedure, and industry guidelines.

General Pressure Testing

This test involves filling a valve body with a testing fluid, which is usually water with a corrosion inhibitor. Then, technicians apply pressure over a specific period of time. The time and level of pressure varies depending on factors including the valve material, valve size, and category of pressure test. But in most cases, the pressure level is higher than the operational/working pressure of the valve. Also, the procedure for the pressure test varies depending on the type of valve in question. Generally, pressure tests aim to ascertain the integrity of the valve shell, seat, and seal against leakages due to pressure. After carrying out a test, a valve will not be accepted if the following occurs:

  • There is any distortion that disrupts the valve operation, due to the test.
  • Visible leaks anywhere in the valve body/bonnet assembly.
  • Leakage via static seals (packing) and gasketed joints, except where permitted by design the test standard.

Common industry guidelines for pressure testing valves can be found in ASME B16.34, API 598, MSS-SP-61, API 527, and ISO . Many tests are recorded on paper wheel charts or manually, although digital options are becoming more prevalent.

Valve Test Read-out Stand, Courtesy: Axcel TS

Hydrostatic vs Pneumatic Pressure Testing

Although water (hydrostatic) is the most common test medium in pressure testing, some conditions require pneumatic pressure testing of valves. For pneumatic testing, air or an inert gas such as nitrogen are the preferred media. Generally, in industry, hydrostatic testing is ideal for high-pressure applications where the equipment is not moisture sensitive.

In situations where moisture can damage certain equipment &#; usually via corrosion &#;  or alter the chemical balance in the system, pneumatic testing is recommended. Also, industry guidelines recommend the use of pneumatic testing for cryogenic and low temperature valves. This is because it is difficult to remove all water after the test. The presence of moisture in an operating system is highly discouraged. The table below highlights more of the differences between hydrostatic and pneumatic testing in line with standards and industry practices.

Are you interested in learning more about Grinding M? Contact us today to secure an expert consultation!

Hydrostatic TestingPneumatic TestingTypically, the system is pressurized to at least 1.5 times above the maximum operating pressure for shell testing, and 1.10 times for seat testing.Because it is used mostly for low-pressure applications, the system is usually pressurized to 10% above the maximum operating value or 100 psi max.The use of pressure-relieving devices is recommended. The use of pressure-relieving devices is mandatory.Requires extensive post-test clean-up to avoid damage to components or disruption to the system when operation begins.There is little or no need for cleaning after testing.Usually records low rates of equipment failure. It sees common equipment failure.The process is straight-forward and poses less danger. Thus, semi-skilled personnel can oversee it.Because of the dangers involved, an experienced operator supervises this process. For example, nitrogen leakage can gradually displace the air in the test lab and affect personnel. Also, the effects of overpressure are more catastrophic. Hydraulic Testing vs. Pneumatic Testing

Note: Testing above 100 psi gas pressure can be very dangerous due to the expansion properties of a gas.

When pressure testing a valve, there are key components that are given a closer look for the duration of the process. Three of these include the shell, seal, and seat.

Shell Testing

The valve shell refers to the main body of the device. Moreover, its testing in the industry is driven mostly by guidelines from API 598 and ASME B16.34. Typically, the valve is mounted on a test bench and partially opened. Then, the shell is pressurized, with ASME B16.34 recommending a minimum of 1.5 times the valve pressure rating at 100 &#; (38 &#;) for hydrostatic testing. While that of pneumatic seat testing is 1.1 times the maximum allowable pressure. Pneumatic testing is done to 80-100 psi. Also, both the API and ASME standards recommend varying test duration depending on the size of the valve being tested. The table below summarizes the test duration.

Valve Size (Inches)Test Duration (Seconds)&#; 2..5 &#; 6..0 &#; 12..0 &#;300Valve Size vs. Test Duration For Shell Test

In addition, the test water temperature should range between 41 &#; (5 &#;) and 122 &#; (50 &#;). And the pressure gauge used for measurements should have calibration ranging from not less than 1.5 times the test pressure, to not more than 4 times the test pressure. For a valve shell to pass the test, there shall be no visible leakage for the duration of the test.

A valve stem seal (packing) is also monitored during the shell test. For adjustable stem seals, the occurrence of leakage during the test is NOT a cause for rejection, as long as the manufacturer can demonstrate the seal&#;s capacity to retain at least the maximum allowable pressure of the valve without any visible leakage. Adjustments to the packing are allowed to eliminate leakage. For non-adjustable stem seals, no leakage is permitted during the shell test.

Seat Testing

Typically, the valve seat test is carried out after testing the valve shell. With the same API and ASME standards as with the shell test providing guidance. The recommended pressure is 110% of the maximum allowable pressure at 100 &#; (38 &#;), and the test time varies with size in accordance with ASME B16.34.

Valve Size (Inches)Test Duration (Seconds)&#; 2..5 &#; 8..0 &#; 18..0 &#;120Valve Size vs. Test Duration For Seat Test

The test duration recommendations from API 598 are similar to these, and it also states the allowable leakage rates from the seat.

Valve Size (Inches)Hydrostatic Leakage Rate (Drops Per Minute)Pneumatic Leakage Rate (Bubbles Per Minute)&#; 2..5 &#; 6..0 &#; 12.

For valve sizes greater than 14 inches, the hydrostatic test leakage rate should not exceed two drops per minute per inch. While the pneumatic test leakage rate should be less than four bubbles per minute per inch.

Fire Testing

One of the requirements of industrial valves is having reliable fire protection. This holds particularly true for sensitive applications such as oil and gas, refinery, and petrochemical industries. Moreover, valves in these industries must guarantee a reliable and safe shut-off in case of a fire incident.

In a fire test, a valve is pressurized and subject to high-temperature flames between &#; (750 &#;) and &#; ( &#;) for a period of thirty minutes. During this period, the heat intensity and the leakages &#; both internal and external &#; are monitored and measured. Also, after extinguishing the flames and allowing the valve to cool, the technician test its pressure-retaining capacity. All through the test, the leakage levels should be within acceptable limits for the valve to pass as being &#;fire-safe&#;. Some key things to note about fire testing include:

  • Leakages from the piping to valve end connections are not part of the acceptance criteria.
  • Technicians measure temperature measurement from at least two places. One is 1&#; (25 mm) from the upper stem packing box on the horizontal centerline, while the other measurement point is 1&#; below the valve.

Standards such as API 607, API 6FA, ISO , BS , and BS constitute industry guidelines for fire testing. On the basis of these guidelines, several companies set up their bespoke procedure for fire-safety valves. Of all the fire testing guidelines, API 607 and API 6FA are the most widely used. API 607 provides testing criteria for valves with non-metallic seating and quarter-turn valves. API 6FA provides the testing criteria for metal seated valves.

Note: Most metal-to-metal seated Gates, Globes, and Swing checks are NOT tested to API 607 due to their inherently Fire Safe Design. (There are no soft parts to melt during a fire.)

Fugitive Emissions Testing

A fugitive emissions test aims to assess the impact of gas or vapor leakage from a valve. Although this leakage can be from anywhere along the piping system, statistics show that approximately 60% of fugitive emissions stem from valves. This data highlights the importance of this test. In addition, the impact of these emissions has significant consequences including:

  • Increase in the risk of fire and explosion.
  • Economic losses due to leakage of the commodity.
  • Long-term health risk to the workers and communities in close proximity.
  • Environmental damage.

When carrying out fugitive emission tests, the most common test gases are helium and methane. The valve is pressurized with the test gas at varying temperatures. Then technicians monitor for leakages via the sniffing or vacuum method. International standards such as API 622, API 624, API 644, ISO -1, and ISO -2 all provide guidance on how to carry out this valve test. However, most organizations develop their specifications to ensure application suitability.

Cryogenic Testing

Cryogenic testing of valves is done for those operating at low temperatures or in cryogenic service. The test procedure involves placing the valve within an insulated tank, with liquid nitrogen at temperatures of down to -320 &#; (-196 &#;).

Then, helium pressurizes the valve to the operating pressure specified for its class. During the test, technicians closely monitor the temperature inside the valve and leakages. In the end, the valve is depressurized and warmed up until it attains ambient temperature. Thereafter, a detailed report summarizes the performance of the valve and whether leakages were within acceptable limits. There are several international standards that provide guidelines for cryogenic valve testing including ISO -1, ISO -2, EN , and BS .

In addition to the standards mentioned in the previous section, there are a host of standards that provide recommendations for different valve types and test procedures. The table below provides a list of these standards and the areas of testing they cover, for quick referencing.

Want more information on Test Bench Valve? Feel free to contact us.

Applicable StandardValve Type and Test Procedure API 598Valve inspection and test. Testing of cast iron gate, plug, check, and globe valves. Also, testing of steel gate, globe, check, ball, and butterfly valves. Cryogenic valves.API 527 and ASME PTC 25Pressure relief valves.API 6DTesting of pipeline valves.ASME B16.34Pressure seal valves and steal valves larger than NPS 24 inches. Flanged, threaded, and welded end of valves.MSS SP-80Bronze gate, globe, angle, and check valves.MSS SP-70, MSS SP-71, MSS SP-78 and MSS SP-85Testing of cast iron valves, flanged, and threaded ends.ISA S-75, ISO , and MSS SP61Hydrostatic testing of valves.FCI 70-2, ISA S-75Control valve testing.Standards for Valve Testing

Comments

Please Join Us to post.

0

0/2000

Guest Posts

If you are interested in sending in a Guest Blogger Submission,welcome to write for us.

Your Name: (required)

Your Email: (required)

Subject:

Your Message: (required)

0/2000